Model Number: 6AV2123-2MB03-0AX0 6AV2123-2GB03-0AX0 6AV2123-2JB03-0AX0 Category: SIEMENS SIMATIC HMI Place of Origin: Made in Germany Warranty: 12 month warranty
SIMATIC HMI Basic Panel TFT display, 65536 colors, PROFINET interface, configurable from WinCC Basic V13/ STEP 7 Basic V13, contains open-source software, which is provided free of charge
SIMATIC HMI Basic Panel TFT display, 65536 colors, PROFINET interface, configurable from WinCC Basic V13/ STEP 7 Basic V13, contains open-source software, which is provided free of charge
General information | |
Product type designation | KTP900 Basic color PN |
Display | |
Design of display | TFT widescreen display, LED backlighting |
Screen diagonal | 9 in |
Display width | 198 mm |
Display height | 111.7 mm |
Number of colors | 65536 |
Resolution (pixels) | |
● Horizontal image resolution ● Vertical image resolution |
800 pixel 480 pixel |
Backlighting | |
● MTBF backlighting (at 25 °C) ● Backlight dimmable |
20 000 h Yes |
Control elements | |
Keyboard fonts | |
● Function keys | |
— Number of function keys | 8 |
— Number of function keys with LEDs | 0 |
● Keys with LED | No |
● System keys | No |
● Numeric keyboard | Yes; Onscreen keyboard |
● alphanumeric keyboard | Yes; Onscreen keyboard |
Touch operation | |
● Design as touch screen | Yes; Analog-resistive |
Installation type/mounting | |
Mounting position | vertical |
Mounting in portrait format possible | Yes |
Mounting in landscape format possible | Yes |
maximum permissible angle of inclination without external | 35° |
ventilation | |
Supply voltage | |
Type of supply voltage | DC |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Input current | |
Current consumption (rated value) |
230 mA 0.2 A²·s |
Starting current inrush I²t | |
Power | |
Active power input, typ. | 5.5 W |
Processor | |
Processor type | ARM |
Memory | |
Flash | Yes |
RAM |
Yes |
Memory available for user data | 10 Mbyte |
Type of output | |
Acoustics ● Buzzer ● Speaker |
No No |
Time of day | |
Clock | |
● Hardware clock (real-time) ● Software clock ● retentive ● synchronizable |
Yes Yes Yes; Back-up duration typically 6 weeks Yes |
Interfaces | |
Number of industrial Ethernet interfaces |
1 0 0 0 1; Up to 16 GB 0 0 0 0 No |
Number of RS 485 interfaces | |
Number of RS 422 interfaces | |
Number of RS 232 interfaces | |
Number of USB interfaces | |
Number of 20 mA interfaces (TTY) | |
Number of parallel interfaces | |
Number of other interfaces | |
Number of SD card slots | |
With software interfaces | |
Industrial Ethernet | |
● Industrial Ethernet status LED | 2 |
Protocols | |
PROFINET |
Yes No No No Yes No |
Supports protocol for PROFINET IO | |
IRT | |
PROFIBUS | |
EtherNet/IP | |
MPI | |
Protocols (Ethernet) | |
● TCP/IP ● DHCP ● SNMP ● DCP ● LLDP |
Yes Yes Yes Yes Yes |
WEB characteristics | |
● HTTP ● HTML |
No No |
Redundancy mode | |
Media redundancy | |
— MRP | No |
Further protocols | |
● CAN ● MODBUS |
No Yes; Modicon (MODBUS TCP/IP) |
Interrupts/diagnostics/status information | |
Diagnoses | |
● Diagnostic information readable | No |
EMC | |
Emission of radio interference acc. to EN 55 011 | |
● Limit class A, for use in industrial areas | Yes |
● Limit class B, for use in residential areas | No |
Degree and class of protection | |
IP (at the front) |
IP65 IP20 Yes Yes |
IP (rear) | |
NEMA (front) ● Enclosure Type 4 at the front ● Enclosure Type 4x at the front |
|
Standards, approvals, certificates | |
CE mark |
Yes Yes Yes Yes |
cULus | |
RCM (formerly C-TICK) | |
KC approval | |
Use in hazardous areas | |
● ATEX Zone 2 ● ATEX Zone 22 ● IECEx Zone 2 ● IECEx Zone 22 ● cULus Class I Zone 1 ● cULus Class I Zone 2, Division 2 ● FM Class I Division 2 |
No No No No No No No |
Marine approval | |
● Germanischer Lloyd (GL) ● American Bureau of Shipping (ABS) ● Bureau Veritas (BV) ● Det Norske Veritas (DNV) ● Lloyds Register of Shipping (LRS) ● Nippon Kaiji Kyokai (Class NK) ● Polski Rejestr Statkow (PRS) ● Chinese Classification Society (CCS) |
Yes Yes Yes Yes Yes Yes No No |
Ambient conditions | |
Ambient temperature during operation | |
Operation (vertical installation) | |
— For vertical installation, min. — For vertical installation, max. |
0 °C 50 °C |
Operation (max. tilt angle) | |
— At maximum tilt angle, min. — At maximum tilt angle, max. |
0 °C 40 °C |
Operation (vertical installation, portrait format) | |
— For vertical installation, min. — For vertical installation, max. |
0 °C 40 °C |
Operation (max. tilt angle, portrait format) | |
— At maximum tilt angle, min. — At maximum tilt angle, max. |
0 °C 35 °C |
Ambient temperature during storage/transportation | |
● min. ● max. |
-20 °C 60 °C |
Relative humidity | |
● Operation, max. | 90 %; no condensation |
Operating systems | |
proprietary | Yes |
pre-installed operating system | |
● Windows CE | No |
configuration / header | |
Message indicator |
Yes Yes Yes Yes Yes |
Alarm system (incl. buffer and acknowledgment) | |
Process value display (output) | |
Process value default (input) possible | |
Recipe management | |
Configuration software | |
● STEP 7 Basic (TIA Portal) ● STEP 7 Professional (TIA Portal) ● WinCC flexible Compact ● WinCC flexible Standard ● WinCC flexible Advanced ● WinCC Basic (TIA Portal) ● WinCC Comfort (TIA Portal) ● WinCC Advanced (TIA Portal) ● WinCC Professional (TIA Portal) |
Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) No No No Yes Yes Yes Yes |
Languages | |
Online languages | |
● Number of online/runtime languages | 10 |
Project languages | |
● Languages per project | 32 |
Functionality under WinCC (TIA Portal) | |
Libraries |
Yes Yes Yes; Available with WinCC (TIA Portal) V14 or higher No Yes No Yes Yes 500 |
Applications/options ● Web browser ● SIMATIC WinCC Sm@rtServer |
|
Number of Visual Basic Scripts | |
Task planner ● time-controlled ● task-controlled |
|
Help system ● Number of characters per info text |
|
Message system | |
● Number of alarm classes ● Bit messages — Number of bit messages ● Analog messages — Number of analog messages ● S7 alarm number procedure ● System messages HMI ● System event, more (SIMATIC S7, SINUMERIK, SIMOTION, ... ) ● Number of characters per message ● Number of process values per message ● Acknowledgment groups ● Message indicator ● Message buffer — Number of entries — Circulating buffer — retentive — maintenance-free |
32 1 000 25 No Yes Yes; System message buffer of the SIMATIC S7-1200 and S7-1500 80 8 Yes Yes 256 Yes Yes Yes |
Recipe management | |
● Number of recipes ● Data records per recipe ● Entries per data record ● Size of internal recipe memory ● Recipe memory expandable |
50 100 100 256 kbyte No |
Variables | |
● Number of variables per device ● Number of variables per screen ● Limit values ● Multiplexing ● Structures ● Arrays |
800 100 Yes Yes No Yes |
Images | |
● Number of configurable images ● Permanent window/default |
250 Yes |
● Global image ● Pop-up images ● Slide-in images ● Image selection by PLC ● Image number in the PLC |
Yes No No Yes Yes |
Image objects | |
● Number of objects per image ● Text fields ● I/O fields ● Graphic I/O fields (graphics list) ● Symbolic I/O fields (text list) ● Date/time fields ● Switches ● Buttons ● Graphic display ● Icons ● Geometric objects |
100 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes |
Complex image objects | |
● Number of complex objects per screen ● Alarm view ● Trend view ● User view ● Status/control ● Sm@rtClient view ● Recipe view ● f(x) trend view ● System diagnostics view ● Media Player ● HTML browser ● PDF display ● IP camera display ● Bar graphs ● Sliders ● Pointer instruments ● Analog/digital clock |
10 Yes Yes Yes No No Yes No Yes; System message buffer of the SIMATIC S7-1200 and S7-1500 No Yes No No Yes No No No |
Lists | |
● Number of text lists per project ● Number of entries per text list ● Number of graphics lists per project ● Number of entries per graphics list |
300 100 100 100 |
Archiving | |
● Number of archives per device ● Number of entries per archive ● Message archive ● Process value archive ● Archiving methods — Sequential archive — Short-term archive ● Memory location — Memory card — USB memory — Ethernet ● Data storage format — CSV — TXT — RDB |
2; One message and one process value archive 10 000 Yes Yes Yes Yes No Yes No No Yes No |
Security | |
● Number of user groups ● Number of user rights ● Number of users |
50 32 50 |
● Password export/import ● SIMATIC Logon |
Yes No |
Character sets | |
● Keyboard fonts — US English |
Yes |
Transfer (upload/download) | |
● MPI/PROFIBUS DP ● USB ● Ethernet ● using external storage medium |
No No Yes Yes |
Process coupling | |
● S7-1200 ● S7-1500 ● S7-200 ● S7-300/400 ● LOGO! ● WinAC ● SINUMERIK ● SIMOTION ● Allen Bradley (EtherNet/IP) ● Allen Bradley (DF1) ● Mitsubishi (MC TCP/IP) ● Mitsubishi (FX) ● OMRON (FINS TCP) ● OMRON (LINK/Multilink) ● Modicon (Modbus TCP/IP) ● Modicon (Modbus) |
Yes Yes Yes Yes Yes Yes Yes; No access to NCK data Yes Yes No Yes No No No Yes No |
Service tools/configuration aids | |
● Backup/Restore manually ● Backup/Restore automatically ● Simulation ● Device switchover |
Yes No Yes Yes |
Peripherals/Options | |
Printer |
No No No No Yes Yes Yes |
SIMATIC HMI MM memory card: Multi Media Card | |
SIMATIC HMI SD memory card: Secure Digital memory card | |
SIMATIC HMI CF memory card Compact Flash Card | |
USB memory | |
SIMATIC IPC USB Flashdrive (USB stick) | |
SIMATIC HMI USB stick | |
Mechanics/material | |
Enclosure material (front) ● Plastic ● Aluminum ● Stainless steel |
Yes No No |
Dimensions | |
Width of the housing front |
267 mm |
Height of housing front | 182 mm |
Mounting cutout, width | 251 mm |
Mounting cutout, height | 166 mm |
Overall depth | 55 mm |
Weights | |
Weight (without packaging) | 1 130 g |