 Model Number: 6ES7288-1ST30-0AA0 6ES7288-1CR40-0AA0 6ES7288-1SR60-0AA0 6ES7288-1CR60-0AA1 6ES7288-5AE01-0AA0 Category: SIEMENS SIMATIC S7-200 SMART Product Type: PLC Module Type: Industry Automation Place of Origin: Made in Germany Warranty: 12 month warranty
*** spare part *** SIMATIC S7-200 SMART, CPU ST30, standard CPU, DC/DC/DC, onboard I/O: 18 DI 24 V DC; 12 DO 24 V DC; power supply: DC 20.4-28.8V DC, program/data memory 30 KB
*** spare part *** SIMATIC S7-200 SMART, CPU ST30, standard CPU, DC/DC/DC, onboard I/O: 18 DI 24 V DC; 12 DO 24 V DC; power supply: DC 20.4-28.8V DC, program/data memory 30 KB
| General information | |
| Product type designation | CPU ST30 DC/DC/DC | 
| Engineering with | |
| ● Programming package | STEP 7 Micro/WIN SMART | 
| Installation type/mounting | |
| Rail mounting | Yes; Standard - DIN rail | 
| Supply voltage | |
| Rated value (DC) | 24 V | 
| permissible range, lower limit (DC) | 20.4 V | 
| permissible range, upper limit (DC) | 28.8 V | 
| Input current | |
| Current consumption, max. | 624 mA; 24 V DC | 
| Inrush current, max. | 6 A; at 28.8 V | 
| Output current | |
| Current output, max. | 300 mA; 24 V DC Sensor Power | 
| for backplane bus (5 V DC), max. | 1.4 A; max. 5 V DC for EM bus | 
| Power loss | |
| Power loss, max. | 12 W | 
| Memory | |
| Type of memory | DDR | 
| Flash | Yes | 
| RAM | Yes | 
| Memory available for user data | 12 kbyte | 
| Memory size | 18 kbyte; Program memory | 
| Micro Memory Card | Yes; microSDHC Card (optional) | 
| Backup | |
| ● present | Yes; Maintenance free, RTC requires 7 days. | 
| CPU processing times | |
| for bit operations, typ. | 150 ns; / instruction | 
| for word operations, typ. | 1.2 µs; / instruction | 
| for floating point arithmetic, typ. | 3.6 µs; / instruction | 
| Address area | |
| I/O address area | |
| ● Inputs ● Outputs | 144 byte; 256 bit of digital inputs & 56 words of analog inputs 144 byte; 256 bit of digital outputs & 56 words of analog outputs | 
| Time of day | |
| Clock | |
| ● Type | Hardware clock, no battery backup | 
|  ● Hardware clock (real-time) ● Backup time ● Deviation per day, max. | Yes 7 d 120 s; within 120s/month at 25 °C | 
| Digital inputs | |
| Number of digital inputs ● of which inputs usable for technological functions | 18 6; HSC (High Speed Counting) Yes | 
| Source/sink input | |
| Number of simultaneously controllable inputs | |
| all mounting positions | |
| — up to 40 °C, max. | 18 | 
| Input voltage | |
| ● Type of input voltage ● Rated value (DC) ● for signal "0" ● for signal "1" | DC 24 V I0.0 to I0.3 < 1 V DC; I0.4 to I2.7 < 5 V DC I0.0 to I0.3 > 4V; I0.4 to I2.7 > 15V | 
| Input current | |
| ● for signal "0", max. (permissible quiescent current) ● for signal "1", typ. | 1 mA 4 mA | 
| Input delay (for rated value of input voltage) | |
| for standard inputs | |
| — parameterizable — at "0" to "1", min. — at "0" to "1", max. | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four 0.2 ms 12.8 ms | 
| for interrupt inputs | |
| — parameterizable | Yes | 
| for technological functions | |
| — parameterizable | Yes; 6 Single phase: 5 HSCs at 200 kHz; 1 HSCs at 30 kHz 4 A/B phase: 3 HSCs at 100 kHz; 1 HSC at 20 kHz | 
| Cable length | |
| ● shielded, max. ● unshielded, max. | 500 m; 50m shielded for HSC inputs 300 m; for technological functions: No | 
| Digital outputs | |
| Number of digital outputs ● of which high-speed outputs | 12; Transistor 3; 100 kHz Pulse Train Output No | 
| Short-circuit protection | |
| Switching capacity of the outputs | |
| ● with resistive load, max. ● on lamp load, max. | 0.5 A 5 W | 
| Output voltage | |
| ● for signal "1", min. | 20 V DC | 
| Output current | |
| ● for signal "1" rated value ● for signal "0" residual current, max. | 0.5 A 10 µA | 
| Output delay with resistive load | |
| ● "0" to "1", max. ● "1" to "0", max. | 3 µs; of the standard outputs, max. 3 µs; of the pulse outputs, max. (Q a.0 to Q a.3) 1 µs 200 µs; of the standard outputs, max. 200 µs; of the pulse outputs, max. (Q a.0 to Q a.3) 50 µs | 
| Switching frequency | |
| ● of the pulse outputs, with resistive load, max. | 100 kHz | 
| Relay outputs | |
| ● Number of relay outputs | 0 | 
| Cable length | |
| ● shielded, max. ● unshielded, max. | 500 m 150 m | 
| Interfaces | |
| Number of industrial Ethernet interfaces | 1 | 
| Number of RS 485 interfaces | 1 | 
| 1. Interface | |
| Interface type | PROFINET | 
| Isolated | Yes; Transformer isolated, 1,500V AC | 
| automatic detection of transmission rate | Yes; 10/100 Mbit/s | 
| Autonegotiation | Yes | 
| Autocrossing | Yes | 
| Interface types | |
| ● RJ 45 (Ethernet) | Yes | 
| Protocols | |
| ● PROFINET IO Controller ● PROFINET IO Device | Yes; Since V2.4 Yes; I-Device since V2.5 | 
| PROFINET IO Controller | |
| ● Transmission rate, max. | 100 Mbit/s | 
| Services | |
| — Number of connectable IO Devices, max. — Updating time | 8 4 ms; The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | 
| Address area | |
| — Inputs, max. — Outputs, max. | 128 byte; Per device 128 byte; Per device | 
| 2. Interface | |
| Interface type | RS 485 (max. 187.5 kbps) | 
| Interface types | |
| ● RS 485 | Yes | 
| PROFIBUS DP master | |
| Services | |
| — S7 communication | Yes | 
| Protocols | |
| Supports protocol for PROFINET IO | Yes; RT Controller (since FW V2.4) & I-Device (since FW V2.5) | 
| PROFIBUS | Yes; Via CM DP module | 
| Protocols (Ethernet) | |
| ● TCP/IP | Yes | 
| communication functions / header | |
| S7 communication | |
| ● supported ● as server ● as client | Yes Yes Yes | 
| Test commissioning functions | |
| Forcing | |
| ● Forcing | Yes | 
| Integrated Functions | |
| Counter ● Number of counters | 6 | 
| PID controller | Yes; PID closed-loop control function: Continuous controller outputs, binary controller outputs, automatic/manual mode, max. 8 loops | 
| Number of pulse outputs | 3 | 
| EMC | |
| Interference immunity against discharge of static electricity | |
| ● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 — Test voltage at air discharge — Test voltage at contact discharge | Yes 8 kV 4 kV | 
| Interference immunity against high-frequency electromagnetic fields | |
| ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 | Yes; 10 V/m, 80 to 1 000 MHz (to IEC 61000-4-3); 10 V/m, 900 MHz, 1.89 GHz, 50% ED (to IEC 61000-4-3) | 
| Interference immunity to cable-borne interference | |
| ● Interference immunity on supply lines acc. to IEC 61000-4-4 ● Interference immunity on signal cables acc. to IEC 61000-4-4 | Yes; 2 kV acc. to IEC 61000-4-4, burst Yes; ±2 kV acc. to IEC 61000-4-4, Burst | 
| Interference immunity against conducted variable disturbance induced by high-frequency fields | |
| ● Interference immunity against high frequency current feed acc. to IEC 61000-4-6 | Yes; 10 V, 150 kHz to 80 MHz (to IEC 61000-4-6) | 
| Emission of radio interference acc. to EN 55 011 | |
| ● Limit class A, for use in industrial areas | Yes; EN 61000-6-4, interference emission: Intended for use in industrial areas. | 
| Emission of conducted and non-conducted interference | |
| ● Interference emission via line/AC current cables | EN 61000-6-4, interference emission: Intended for use in industrial areas. | 
| Degree and class of protection | |
| IP degree of protection | IP20 | 
| Standards, approvals, certificates | |
| CE mark | Yes | 
| Ambient conditions | |
| Free fall | |
| ● Fall height, max. | 0.3 m; five times, in product package | 
| Ambient temperature during operation | |
| ● min. ● max. ● horizontal installation, min. ● horizontal installation, max. ● vertical installation, min. ● vertical installation, max. | 0 °C 55 °C 0 °C 55 °C 0 °C 45 °C | 
| Ambient temperature during storage/transportation | |
| ● min. ● max. | -40 °C 70 °C | 
| Air pressure acc. to IEC 60068-2-13 | |
| ● Storage/transport, min. ● Storage/transport, max. | 660 hPa 1 080 hPa | 
| Altitude during operation relating to sea level | |
| ● Installation altitude, min. ● Installation altitude, max. | -1 000 m 2 000 m | 
| Relative humidity | |
| ● Operation at 25 ℃ without condensation, max. | 95 % | 
| configuration / header | |
| configuration / programming / header | |
| Programming language | |
| — LAD — FBD — STL | Yes Yes Yes | 
| Dimensions | |
| Width | 110 mm | 
| Height | 100 mm | 
| Depth | 81 mm | 
| Weights | |
| Weight, approx. | 375 g | 
    
| 6ES7288-1CR20-0AA1 | 6ES7288-1CR40-0AA1 | 6ES7288-1ST20-0AA0 | 
| 6ES7288-1ST30-0AA0 | 6ES7288-1ST40-0AA0 | 6ES7288-1ST60-0AA0 | 
| 6ES7288-1CR40-0AA0 | 6ES7288-1CR60-0AA0 | 6ES7288-1SR40-0AA0 | 
| 6ES7288-1SR60-0AA0 | 6ES7288-1SR20-0AA0 | 6ES7288-1SR30-0AA0 | 
| 6ES7288-1ST20-0AA1 | 6ES7288-1ST60-0AA1 | 6ES7288-1ST40-0AA1 | 
| 6ES7288-1SR60-0AA1 | 6ES7288-1SR30-0AA1 | 6ES7288-1SR20-0AA1 | 
| 6ES7288-1SR40-0AA1 | 6ES7288-1ST30-0AA1 | 6ES7288-1SR20-0AA1 | 
| 6ES7288-5DT04-0AA0 | 6ES7288-5BA01-0AA0 | 6ES7288-1ST20-0AA0 | 
| 6ES7288-1ST60-0AA0 | 6ES7288-1SR40-0AA0 | 6ES7288-1SR30-0AA0 | 
| 6ES7288-1SR20-0AA0 | 6ES7288-5AQ01-0AA0 | 6ES7288-1ST40-0AA0 | 
| 6ES7288-1ST30-0AA0 | 6ES7288-1CR40-0AA0 | 6ES7288-1SR60-0AA0 | 
| 6ES7288-1CR60-0AA1 | 6ES7288-5AE01-0AA0 | 6ES7288-1CR60-0AA0 | 
| 6ES7288-1CR30-0AA1 | 6ES7288-6EC01-0AA0 | 6ES7288-5CM01-0AA0 | 
| 6ES7288-5DT04-0AA0 | 6ES7288-5AE01-0AA0 | 6ES7288-5AQ01-0AA0 | 
| 6ES7288-5BA01-0AA0 | 
    
 
    
     
    