 Model Number: 6ES7215-1AG40-0XB0 6ES7214-1BG40-0XB0 6ES7214-1HG40-0XB0 6ES7212-1HF41-4YB1 6ES7214-1AG40-0XB0 6ES7215-1BG40-0XB0 Category: SIEMENS SIMATIC S7-1200F CPU Product Type: PLC Type: Industry Automation Place of Origin: Made in Germany Warranty: 12 month warranty
SIMATIC S7-1200, CPU 1215C, compact CPU, DC/DC/DC, 2 PROFINET ports, onboard I/O: 14 DI 24 V DC; 10 DO 24 V DC; 0.5A; 2 AI 0-10 V DC, 2 AO 0-20 mA DC, Power supply: DC 20.4-28.8V DC, Program/data memory 125 KB
SIMATIC S7-1200, CPU 1215C, compact CPU, DC/DC/DC, 2 PROFINET ports, onboard I/O: 14 DI 24 V DC; 10 DO 24 V DC; 0.5A; 2 AI 0-10 V DC, 2 AO 0-20 mA DC, Power supply: DC 20.4-28.8V DC, Program/data memory 125 KB
| General information | |
| Product type designation | CPU 1211C AC/DC/relay | 
| Firmware version | V4.5 | 
| Engineering with | |
| ● Programming package | STEP 7 V17 or higher | 
| Supply voltage | |
| Rated value (AC) ● 120 V AC ● 230 V AC | Yes Yes | 
| permissible range, lower limit (AC) | 85 V | 
| permissible range, upper limit (AC) | 264 V | 
| Line frequency | |
| ● permissible range, lower limit ● permissible range, upper limit | 47 Hz 63 Hz | 
| Input current | |
| Current consumption (rated value) | 60 mA at 120 V AC; 30 mA at 240 V AC | 
| Current consumption, max. | 180 mA at 120 V AC; 90 mA at 240 V AC | 
| Inrush current, max. | 20 A; at 264 V | 
| I²t | 0.8 A²·s | 
| Output current | |
| for backplane bus (5 V DC), max. | 750 mA; Max. 5 V DC for CM | 
| Encoder supply | |
| 24 V encoder supply | |
| ● 24 V | 20.4 to 28.8V | 
| Power loss | |
| Power loss, typ. | 10 W | 
| Memory | |
| Work memory | |
| ● integrated ● expandable | 50 kbyte No | 
| Load memory | |
| ● integrated ● Plug-in (SIMATIC Memory Card), max. | 1 Mbyte with SIMATIC memory card | 
| Backup | |
| ● present ● maintenance-free ● without battery | Yes Yes Yes | 
| CPU processing times | |
| for bit operations, typ. | 0.08 µs; / instruction | 
| for word operations, typ. | 1.7 µs; / instruction | 
| for floating point arithmetic, typ. | 2.3 µs; / instruction | 
| CPU-blocks | |
| Number of blocks (total) | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | 
| OB | |
| ● Number, max. | Limited only by RAM for code | 
| Data areas and their retentivity | |
| Retentive data area (incl. timers, counters, flags), max. | 14 kbyte | 
| Flag | |
| ● Size, max. | 4 kbyte; Size of bit memory address area | 
| Local data | |
| ● per priority class, max. | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 
| Address area | |
| Process image | |
| ● Inputs, adjustable ● Outputs, adjustable | 1 kbyte 1 kbyte | 
| Hardware configuration | |
| Number of modules per system, max. | 3 communication modules, 1 signal board | 
| Time of day | |
| Clock | |
| ● Hardware clock (real-time) ● Backup time ● Deviation per day, max. | Yes 480 h; Typical ±60 s/month at 25 °C | 
| Digital inputs | |
| Number of digital inputs ● of which inputs usable for technological functions | 6; Integrated 6; HSC (High Speed Counting) | 
| Source/sink input | Yes | 
| Number of simultaneously controllable inputs | |
| all mounting positions | |
| — up to 40 °C, max. | 6 | 
| Input voltage | |
| ● Rated value (DC) ● for signal "0" ● for signal "1" | 24 V 5 V DC at 1 mA 15 V DC at 2.5 mA | 
| Input current | |
| ● for signal "1", typ. | 4 mA; nominal | 
| Input delay (for rated value of input voltage) | |
| for standard inputs | |
| — parameterizable — at "0" to "1", min. — at "0" to "1", max. | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four 0.2 ms 12.8 ms | 
| for interrupt inputs | |
| — parameterizable | Yes | 
| for technological functions | |
| — parameterizable | Single phase : 3 @ 100 kHz, differential: 3 @ 80 kHz | 
| Cable length | |
| ● shielded, max. ● unshielded, max. | 500 m; 50 m for technological functions 300 m; for technological functions: No | 
| Digital outputs | |
| Number of digital outputs | 4; Relays | 
| Switching capacity of the outputs | |
| ● with resistive load, max. ● on lamp load, max. | 2 A 30 W with DC, 200 W with AC | 
| Output delay with resistive load | |
| ● "0" to "1", max. ● "1" to "0", max. | 10 ms; max. 10 ms; max. | 
| Relay outputs | |
| ● Number of relay outputs ● Number of operating cycles, max. | 4 mechanically 10 million, at rated load voltage 100 000 | 
| Cable length | |
| ● shielded, max. ● unshielded, max. | 500 m 150 m | 
| Analog inputs | |
| Number of analog inputs | 2 | 
| Input ranges | |
| ● Voltage | Yes | 
| Input ranges (rated values), voltages | |
| ● 0 to +10 V — Input resistance (0 to 10 V) | Yes ≥100k ohms | 
| Cable length | |
| ● shielded, max. | 100 m; twisted and shielded | 
| Analog outputs | |
| Number of analog outputs | 0 | 
| Analog value generation for the inputs | |
| Integration and conversion time/resolution per channel | |
| ● Resolution with overrange (bit including sign), max. ● Integration time, parameterizable ● Conversion time (per channel) | 10 bit Yes 625 µs | 
| Encoder | |
| Connectable encoders | |
| ● 2-wire sensor | Yes | 
| 1. Interface | |
| Interface type | PROFINET | 
| Isolated | Yes | 
| automatic detection of transmission rate | Yes | 
| Autonegotiation | Yes | 
| Autocrossing | Yes | 
| Interface types | |
| ● RJ 45 (Ethernet) ● Number of ports ● integrated switch | Yes 1 No | 
| Protocols | |
| ● PROFINET IO Controller ● PROFINET IO Device ● SIMATIC communication ● Open IE communication ● Web server ● Media redundancy | Yes Yes Yes Yes; Optionally also encrypted Yes No | 
| PROFINET IO Controller | |
| ● Transmission rate, max. | 100 Mbit/s | 
| Services | |
| — PG/OP communication — Isochronous mode — IRT — PROFIenergy — Prioritized startup — Number of IO devices with prioritized startup, max. — Number of connectable IO Devices, max. — Number of connectable IO Devices for RT, max. — of which in line, max. — Activation/deactivation of IO Devices — Number of IO Devices that can be | Yes; encryption with TLS V1.3 pre-selected No No No Yes 16 16 16 16 Yes 8 | 
| simultaneously activated/deactivated, max. — Updating time | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | 
| PROFINET IO Device | |
| Services | |
| — PG/OP communication — Isochronous mode — IRT — PROFIenergy — Shared device — Number of IO Controllers with shared device, max. | Yes; encryption with TLS V1.3 pre-selected No No Yes Yes 2 | 
| Protocols | |
| Supports protocol for PROFINET IO | Yes | 
| PROFIsafe | No | 
| PROFIBUS | Yes; CM 1243-5 (master) or CM 1242-5 (slave) required | 
| OPC UA | Yes; OPC UA Server | 
| AS-Interface | Yes; CM 1243-2 required | 
| Protocols (Ethernet) | |
| ● TCP/IP ● DHCP ● SNMP ● DCP ● LLDP | Yes No Yes Yes Yes | 
| Redundancy mode | |
| Media redundancy | |
| — MRP — MRPD | No No | 
| SIMATIC communication | |
| ● S7 routing | Yes | 
| Open IE communication | |
| ● TCP/IP — Data length, max. — several passive connections per port, supported ● ISO-on-TCP (RFC1006) — Data length, max. ● UDP — Data length, max. | Yes 8 kbyte Yes Yes 8 kbyte Yes 1 472 byte | 
| Web server | |
| ● supported ● User-defined websites | Yes Yes | 
| OPC UA | |
| ● Runtime license required ● OPC UA Server — Application authentication — User authentication — Number of sessions, max. — Number of subscriptions per session, max. — Sampling interval, min. — Publishing interval, min. — Number of server methods, max. — Number of monitored items, max. — Number of server interfaces, max. — Number of nodes for user-defined server interfaces, max. | Yes; "Basic" license required Yes; data access (read, write, subscribe), method call, runtime license required Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 "anonymous" or by user name & password 10 50 100 ms 200 ms 20 1 000 2 2 000 | 
| Further protocols | |
| ● MODBUS | Yes | 
| communication functions / header | |
| S7 communication | |
| ● supported ● as server ● as client ● User data per job, max. | Yes Yes Yes See online help (S7 communication, user data size) | 
| Number of connections | |
| ● overall | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 64 max | 
| Test commissioning functions | |
| Status/control | |
| ● Status/control variable ● Variables | Yes Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | 
| Forcing | |
| ● Forcing | Yes | 
| Diagnostic buffer | |
| ● present | Yes | 
| Traces | |
| ● Number of configurable Traces ● Memory size per trace, max. | 2 512 kbyte | 
| Interrupts/diagnostics/status information | |
| Diagnostics indication LED | |
| ● RUN/STOP LED ● ERROR LED ● MAINT LED | Yes Yes Yes | 
| Integrated Functions | |
| Counter ● Number of counters ● Counting frequency, max. | 6 100 kHz Yes | 
| Frequency measurement | Yes | 
| controlled positioning | Yes | 
| Number of position-controlled positioning axes, max. | 8 | 
| Number of positioning axes via pulse-direction interface | Up to 4 with SB 1222 | 
| PID controller | Yes | 
| Number of alarm inputs | 4 | 
| Potential separation | |
| Potential separation digital inputs | |
| ● Potential separation digital inputs ● between the channels, in groups of | 500V AC for 1 minute 1 | 
| Potential separation digital outputs | |
| ● Potential separation digital outputs ● between the channels ● between the channels, in groups of | Relays No 1 | 
| EMC | |
| Interference immunity against discharge of static electricity | |
| ● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 — Test voltage at air discharge — Test voltage at contact discharge | Yes 8 kV 6 kV | 
| Interference immunity to cable-borne interference | |
| ● Interference immunity on supply lines acc. to IEC 61000-4-4 ● Interference immunity on signal cables acc. to IEC 61000-4-4 | Yes Yes | 
| Interference immunity against voltage surge | |
| ● Interference immunity on supply lines acc. to IEC 61000-4-5 | Yes | 
| Interference immunity against conducted variable disturbance induced by high-frequency fields | |
| ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 | Yes | 
| Emission of radio interference acc. to EN 55 011 | |
| ● Limit class A, for use in industrial areas ● Limit class B, for use in residential areas | Yes; Group 1 Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | 
| Degree and class of protection | |
| IP degree of protection | IP20 | 
| Standards, approvals, certificates | |
| CE mark | Yes | 
| UL approval | Yes | 
| cULus | Yes | 
| FM approval | Yes | 
| RCM (formerly C-TICK) | Yes | 
| KC approval | Yes | 
| Marine approval | Yes | 
| Ambient conditions | |
| Free fall | |
| ● Fall height, max. | 0.3 m; five times, in product package | 
| Ambient temperature during operation | |
| ● min. ● max. ● horizontal installation, min. ● horizontal installation, max. ● vertical installation, min. ● vertical installation, max. | -20 °C 60 °C -20 °C 60 °C -20 °C 50 °C | 
| Ambient temperature during storage/transportation | |
| ● min. ● max. | -40 °C 70 °C | 
| Air pressure acc. to IEC 60068-2-13 | |
| ● Operation, min. ● Operation, max. ● Storage/transport, min. ● Storage/transport, max. | 795 hPa 1 080 hPa 660 hPa 1 080 hPa | 
| Altitude during operation relating to sea level | |
| ● Installation altitude, min. ● Installation altitude, max. | -1 000 m 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 
| Relative humidity | |
| ● Operation, max. | 95 %; no condensation | 
| Vibrations | |
| ● Vibration resistance during operation acc. to IEC 60068-2-6 ● Operation, tested according to IEC 60068-2-6 | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail Yes | 
| Shock testing | |
| ● tested according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | 
| Pollutant concentrations | |
| ● SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | 
| configuration / header | |
| configuration / programming / header | |
| Programming language | |
| — LAD — FBD — SCL | Yes Yes Yes | 
| Know-how protection | |
| ● User program protection/password protection ● Copy protection ● Block protection | Yes Yes Yes | 
| Access protection | |
| ● protection of confidential configuration data | Yes | 
|   | |
| ● Protection level: Write protection ● Protection level: Read/write protection ● Protection level: Complete protection | Yes Yes Yes | 
| programming / cycle time monitoring / header | |
| ● cycle monitoring time / adjustable | Yes | 
| Dimensions | |
| Width | 90 mm | 
| Height | 100 mm | 
| Depth | 75 mm | 
| Weights | |
| Weight, approx. | 420 g | 
    
| 6ES7214-1AF40-0XB0 | 6ES7212-1AE40-0XB0 | 6ES7214-1HF40-0XB0 | 
| 6ES7212-1HF40-0XB0 | 6ES7212-1AF40-0XB0 | 6ES7215-1HF40-0XB0 | 
| 6ES7215-1AF40-0XB0 | 6ES7211-1HE40-0XB0 | 6ES7212-1BE40-0XB0 | 
| 6ES7212-1HE40-0XB0 | 6ES7211-1BE40-0XB0 | 6ES7211-1AE40-0XB0 | 
| 6ES7212-1HF42-4YB1 | 6ES7217-1AG40-0XB0 | 6ES7215-1HG40-0XB0 | 
| 6ES7215-1AG40-0XB0 | 6ES7214-1BG40-0XB0 | 6ES7214-1HG40-0XB0 | 
| 6ES7212-1HF41-4YB1 | 6ES7214-1AG40-0XB0 | 6ES7215-1BG40-0XB0 | 
    
 
    
     
    