 Model Number: 6ES7288-2DR32-0AA0 6ES7288-3AE04-0AA0 6ES7288-3AQ02-0AA0 6ES7288-2DT08-0AA0 Category: SIEMENS SIMATIC S7-200 SMART Product Type: PLC Module Type: Industry Automation Place of Origin: Made in Germany Warranty: 12 month warranty
SIMATIC S7-200 SMART, Digital I/O SM DR32, 16DI/16DO, 16 DI 24 V DC, Sink/Source, 16 DO, relay 2 A
SIMATIC S7-200 SMART, Digital I/O SM DR32, 16DI/16DO, 16 DI 24 V DC, Sink/Source, 16 DO, relay 2 A
| General information | |
| Product type designation | SM DR32, DI 16x24 V DC, DQ 16x relay/2A | 
| Supply voltage | |
| Rated value (DC) | 24 V | 
| permissible range, lower limit (DC) | 20.4 V | 
| permissible range, upper limit (DC) | 28.8 V | 
| Input current | |
| Current consumption, typ. | 165 mA; Current for 24 V DC input power 165 mA; For 5 V DC from CPU module | 
| from backplane bus 5 V DC, typ. | |
| Digital inputs | |
| Number of digital inputs ● in groups of | 16 2 | 
| Parallel switching of inputs | Yes | 
| Input characteristic curve in accordance with IEC 61131, type 1 | Yes | 
| Number of simultaneously controllable inputs | |
| horizontal installation | |
| — up to 50 °C, max. | 16 | 
| vertical installation | |
| — up to 40 °C, max. | 16 | 
| Input voltage | |
| ● Type of input voltage ● Rated value (DC) ● for signal "0" ● for signal "1" | DC 24 V < 5 V DC +15 to +30 V | 
| Input current | |
| ● for signal "0", max. (permissible quiescent current) ● for signal "1", min. ● for signal "1", max. ● for signal "1", typ. | 1 mA 2.5 mA 5 mA 4 mA | 
| Input delay (for rated value of input voltage) | |
| for standard inputs | |
| — at "0" to "1", max. — at "1" to "0", max. | 200 µs 200 µs | 
| Cable length | |
| ● shielded, max. ● unshielded, max. | 500 m 300 m | 
| Digital outputs | |
| Number of digital outputs | 16 | 
| Short-circuit protection | No | 
| Output current | |
| ● for signal "1" rated value | 2 A | 
| Output delay with resistive load | |
| ● "0" to "1", max. ● "1" to "0", max. | 10 ms 10 ms | 
| Relay outputs | |
| ● Number of relay outputs ● Rated supply voltage of relay coil L+ (DC) — Reverse polarity protection ● Current consumption of relays (coil current of all relays), max. | 16 24 V Yes 165 mA | 
| Switching capacity of contacts | |
| — with inductive load, max. — on lamp load, max. — with resistive load, up to 50 °C, max. — with resistive load, up to 60 °C, max. — with resistive load, max. — Thermal continuous current, max. | 2 A 30 W; 30 W with DC, 200 W with AC 2 A 2 A 2 A 2 A | 
| Cable length | |
| ● shielded, max. ● unshielded, max. | 500 m 150 m | 
| Interrupts/diagnostics/status information | |
| Diagnostics indication LED | |
| ● for status of the inputs ● for status of the outputs | Yes Yes | 
| Potential separation | |
| Potential separation digital inputs | |
| ● between the channels | Yes; Optocoupler | 
| Potential separation digital outputs | |
| ● between the channels | Yes; Relay, dry contact | 
| Isolation | |
| Isolation tested with | 500 V AC for 1 minute for input isolation; 1500 V AC for 1 minute for output isolation | 
| EMC | |
| Interference immunity against discharge of static electricity | |
| ● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 — Test voltage at air discharge — Test voltage at contact discharge | Yes; ±4 kV contact discharge (to IEC 801-2/IEC 1000-4-2; ESD), ±8 kV air discharge (to IEC 801-2/IEC 1000-4-2; ESD) 8 kV 4 kV | 
| Interference immunity against high-frequency electromagnetic fields | |
| ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 — Frequency range of the RF radiation | Yes 80 to 1000 MHz, 10 V/m, 1.4 to 2.0 GHz, 3 V/m, 2.0 to 2.7 GHz, 1 V/m(In the range of 87 MHz to 187 MHz, 174 MHz to 230 MHz and 470 MHz to 790 MHz: 3V/m ) | 
| Interference immunity to cable-borne interference | |
| ● Interference immunity on supply lines acc. to IEC 61000-4-4 ● Interference immunity on signal cables acc. to IEC 61000-4-4 | Yes; 2 kV acc. to IEC 61000-4-4, burst Yes; ±2 kV acc. to IEC 61000-4-4, Burst | 
| Interference immunity against voltage surge | |
| ● Interference immunity on supply lines acc. to IEC 61000-4-5 ● asymmetric interference — Test voltage on supply cables — Test voltage on signal cables >30m | Yes; With upstream protective element 2 kV 2 kV | 
| Interference immunity against conducted variable disturbance induced by high-frequency fields | |
| ● Interference immunity against high frequency current feed acc. to IEC 61000-4-6 ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 | Yes Yes; 10 V/m, with 80% amplitude modulation at 1 kHz | 
| — Test voltage at 80% amplitude modulation with 1kHz in the range 9 kHz to 80 MHz | 10 V | 
| Emission of radio interference acc. to EN 55 011 | |
| ● Emission of radio interference ● Limit class A, for use in industrial areas | Interference emission to EN 50081-2, testing to EN 55011, Class A, Group 1 Yes | 
| Degree and class of protection | |
| IP degree of protection | IP20 | 
| Standards, approvals, certificates | |
| CE mark | Yes | 
| Dimensions | |
| Width | 70 mm | 
| Height | 100 mm | 
| Depth | 81 mm | 
| Weights | |
| Weight, approx. | 295.4 g | 
    
| 6ES7288-3AQ04-0AA0 | 6ES7288-3AT04-0AA0 | 6ES7288-2DE08-0AA0 | 
| 6ES7288-2DT32-0AA0 | 6ES7288-2DR32-0AA0 | 6ES7288-3AE04-0AA0 | 
| 6ES7288-3AQ02-0AA0 | 6ES7288-2DT08-0AA0 | 6ES7288-3AR04-0AA0 | 
| 6ES7288-3AE08-0AA0 | 6ES7288-3AM03-0AA0 | 6ES7288-3AM06-0AA0 | 
| 6ES7288-2DT16-0AA0 | 6ES7288-3AR02-0AA0 | 6ES7288-2DR16-0AA0 | 
| 6ES7288-2DR08-0AA0 | 
    
 
    
     
    