Model Number: 6ES7313-5BG04-4AB2 6ES7313-6CG04-4AB1 6ES7314-6CH04-4AB2 Category: SIEMENS SIMATIC S7-300 CPU Product Type: CPU Type: Industry Automation Place of Origin: Made in Germany Warranty: 12 month warranty
SIMATIC S7-300 CPU bundle Consisting of: S7-300 CPU 313C (6ES7313-5BG04-0AB0), 2x front connectors (6ES7392-1BM01-0AA0) with spring-loaded contacts, 40-pole
SIMATIC S7-300 CPU bundle Consisting of: S7-300 CPU 313C (6ES7313-5BG04-0AB0), 2x front connectors (6ES7392-1BM01-0AA0) with spring-loaded contacts, 40-pole
General information | |||
HW functional status |
01 |
||
Firmware version | V3.3 | ||
Product function | |||
● Isochronous mode | Yes; For PROFINET only | ||
Engineering with | |||
● Programming package | STEP 7 V5.5 or higher with HSP 191 | ||
Supply voltage | |||
Rated value (DC) | 24 V | ||
permissible range, lower limit (DC) | 19.2 V | ||
permissible range, upper limit (DC) | 28.8 V | ||
external protection for power supply lines (recommendation) |
Miniature circuit breaker, type C; min. 2 A; miniature circuit breaker type B, min. 4 A |
||
Mains buffering | |||
● Mains/voltage failure stored energy time ● Repeat rate, min |
5 ms 1 s |
||
Load voltage L+ | |||
● Rated value (DC) ● Reverse polarity protection |
24 V Yes |
||
Digital outputs | |||
— Rated value (DC) — Reverse polarity protection |
24 V; No; |
||
Input current | |||
Current consumption (rated value) | 850 mA | ||
Current consumption (in no-load operation), typ. | 190 mA | ||
Inrush current, typ. | 5 A | ||
I²t | 0.7 A²·s | ||
Digital inputs | |||
● from load voltage L+ (without load), max | 80 mA | ||
Digital outputs | |||
● from load voltage L+, max. | 50 mA | ||
Power loss | |||
Power loss, typ. | 14 W | ||
Memory | |||
Work memory | |||
● integrated ● expandable |
192 kbyte No |
||
Load memory | |||
● Plug-in (MMC) ● Plug-in (MMC), max. ● Data management on MMC (after last programming), min. |
Yes 8 Mbyte 10 y |
||
Backup | |||
● present ● without battery |
Yes; Guaranteed by MMC (maintenance-free) Yes; Program and data |
||
CPU processing times | |||
for bit operations, typ. | 0.06 µs | ||
for word operations, typ. | 0.12 µs | ||
for fixed point arithmetic, typ. | 0.16 µs | ||
for floating point arithmetic, typ. | 0.59 µs | ||
CPU-blocks | |||
Number of blocks (total) | 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. | ||
DB | |||
● Number, max. ● Size, max. |
1024; Number range: 1 to 16000 64 kbyte |
||
FB | |||
● Number, max. ● Size, max. |
1024; Number range: 0 to 7999 64 kbyte |
||
FC | |||
● Number, max. ● Size, max. |
1024; Number range: 0 to 7999 64 kbyte |
||
OB | |||
● Number, max. ● Size, max. ● Number of free cycle OBs ● Number of time alarm OBs ● Number of delay alarm OBs ● Number of cyclic interrupt OBs ● Number of process alarm OBs ● Number of DPV1 alarm OBs ● Number of isochronous mode OBs ● Number of technology synchronous alarm OBs ● Number of startup OBs ● Number of asynchronous error OBs ● Number of synchronous error OBs |
see instruction list 64 kbyte 1; OB 1 1; OB 10 2; OB 20, 21 4; OB 32, 33, 34, 35 1; OB 40 3; OB 55, 56, 57 1; OB 61; only for PROFINET 1; OB 65 1; OB 100 6; OB 80, 82, 83, 85, 86, 87 (OB83 only for PROFINET IO) 2; OB 121, 122 |
||
Nesting depth | |||
● per priority class ● additional within an error OB |
16 4 |
||
Counters, timers and their retentivity | |||
S7 counter | |||
● Number | 256 | ||
Retentivity | |||
— adjustable — lower limit — upper limit — preset |
Yes 0 255 No retentivity |
||
Time range | |||
— loer limit — upper limit |
10 ms 9990 s |
||
IEC counter | |||
● present ● Type ● Number |
Yes SFB Unlimited (limited only by RAM capacity) |
||
S7 times | |||
● Number | 512 | ||
Retentivity | |||
— adjustable — lower limit — upper limit — preset |
Yes 0 511 No retentivity |
||
Time range | |||
— lower limit | 10 ms | ||
— upper limit | 9 990 s | ||
IEC timer | |||
● present ● Type ● Number |
Yes SFB Unlimited (limited only by RAM capacity) |
||
Data areas and their retentivity | |||
Retentive data area (incl. timers, counters, flags), max. | 64 kbyte | ||
Flag | |||
● Size, max. ● Retentivity available ● Retentivity preset ● Number of clock memories |
256 byte Yes; From MB 0 to MB 255 MB 0 to MB 15 8; 1 memory byte |
||
Data blocks | |||
● Retentivity adjustable ● Retentivity preset |
Yes; via non-retain property on DB Yes |
||
Local data | |||
● per priority class, max. | 32 byte; Max. 2048 bytes per block | ||
Address area | |||
I/O address area | |||
● Inputs ● Outputs |
2048 byte 2048 byte |
||
of which distributed | |||
— Inputs — Outputs |
2003 byte 2010 byte |
||
Process image | |||
● Inputs ● Outputs ● Inputs, adjustable ● Outputs, adjustable ● Inputs, default ● Outputs, default |
2048 byte 2048 byte 2048 byte 2048 byte 256 byte 256 byte |
||
Default addresses of the integrated channels | |||
— Digital inputs — Digital outputs — Analog inputs — Analog outputs |
136.0 to 138.7 136.0 to 137.7 800 to 809 800 to 803 |
||
Subprocess images | |||
● Number of subprocess images, max. | 1; With PROFINET IO, the length of the user data is limited to 1600 bytes | ||
Digital channels | |||
● Inputs — of which central ● Outputs — of which central |
16 048 1 016 16096 1008 |
||
Analog channels | |||
● Inputs — of which central ● Outputs — of which central |
1006 253 1007 250 |
||
Hardware configuration | |||
Number of expansion units, max. | 3 | ||
Number of DP masters | |||
● integrated ● via CP |
1 4 |
||
Number of operable FMs and CPs (recommended) | |||
● FM ● CP, PtP ● CP, LAN |
8 8 10 |
||
Rack | |||
● Racks, max. ● Modules per rack, max. |
4 8; In rack 3 max. 7 |
||
Time of day | |||
Clock | |||
● Hardware clock (real-time) ● retentive and synchronizable ● Backup time ● Deviation per day, max. ● Behavior of the clock following POWER-ON ● Behavior of the clock following expiry of backup period |
Yes Yes 6 wk; At 40 °C ambient temperature 10 s; Typ.: 2 s Clock continues running after POWER OFF the clock continues at the time of day it had when power was switched offoff |
||
Operating hours counter | |||
● Number | 1 | ||
● Number/Number range | 0 | ||
● Range of values | 0 to 2^31 hours (when using SFC 101) | ||
● Granularity | 1 h | ||
● retentive | Yes; Must be restarted at each restart | ||
Clock synchronization | |||
● supported | Yes | ||
● to MPI, master | Yes | ||
● to MPI, slave | Yes | ||
● to DP, master | Yes | ||
● to DP, slave | Yes; With DP slave only slave clock | ||
● in AS, master | Yes | ||
● in AS, slave | Yes | ||
● on Ethernet via NTP | Yes; As client | ||
Digital inputs | |||
Number of digital inputs | 24 | ||
● of which inputs usable for technological functions | 16 | ||
integrated channels (DI) | 24 | ||
Input characteristic curve in accordance with IEC 61131, | Yes | ||
type 1 | |||
Number of simultaneously controllable inputs | |||
horizontal installation | |||
— up to 40 °C, max. | 24 | ||
— up to 60 °C, max. | 12 | ||
vertical installation | |||
— up to 40 °C, max. | 12 | ||
Input voltage | |||
● Rated value (DC) ● for signal "0" ● for signal "1" |
24 V -3 to +5V +15 to +30 V |
||
Input current | |||
● for signal "1", typ. | 8 mA | ||
Input delay (for rated value of input voltage) | |||
for standard inputs | |||
— parameterizable |
Yes; 0.1 / 0.3 / 3 / 15 ms (You can reconfigure the input delay of the standard inputs during program runtime. Please note that under certain circumstances your newly set filter time may not be effective until the next filter cycle.) |
||
— Rated value | 3 ms | ||
for technological functions |
|||
— at "0" to "1", max. |
8 µs; Minimum pulse width/minimum pause between pulses at maximum counting frequency |
||
Cable length | |||
● shielded, max. ● unshielded, max. |
1 000 m; 50 m for technological functions 600 m; for technological functions: No |
||
for technological functions | |||
shielded, max. unshielded, max. |
50 m; at maximum count frequency not alloed |
||
Digital outputs | |||
Number of digital outputs | 16 | ||
● of which high-speed outputs | 4; Notice: You cannot connect the fast outputs of your CPU in parallel | ||
Functions | for technology functions, e.g. high-speed cam switch signals | ||
Short-circuit protection | Yes | ||
● Response threshold, typ. | 1 A | ||
Limitation of inductive shutdown voltage to | L+ (-48 V) | ||
Controlling a digital input |
Yes |
||
Switching capacity of the outputs | |||
● on lamp load, max. | 5 W | ||
Load resistance range | |||
● lower limit ● upper limit |
48 Ω 4 kΩ |
||
Output voltage | |||
● for signal "0", max. ● for signal "1", min. |
L+ (-0.8 V) | ||
Output current | |||
● for signal "1" rated value ● for signal "1" permissible range, min. ● for signal "1" permissible range, max. ● for signal "1" minimum load current ● for signal "0" residual current, max |
0.5 A 5 mA 0.6 A 5 mA 0.5 mA |
||
Parallel switching of two outputs | |||
● for uprating ● for redundant control of a load |
No Yes |
||
Switching frequency | |||
● with resistive load, max. ● with inductive load, max. ● on lamp load, max. ● of the pulse outputs, with resistive load, max |
100 Hz 0.5 Hz 100 Hz 2.5 kHz |
||
Total current of the outputs (per group) | |||
horizontal installation | |||
— up to 40 °C, max. — up to 60 °C, max. |
3 A 2 A |
||
all other mounting positions | |||
— up to 40 °C, max. | 2 A | ||
Integrated high-speed cams | |||
● Switching accuracy (+/-) | 70 µs | ||
Cable length | |||
● shielded, max. ● unshielded, max. |
1 000 m 600 m |
||
Number of analog inputs | 0 |
● 2-wire sensor — permissible quiescent current (2-wire sensor), max. |
Yes 1.5 mA |
Errors/accuracies | |
Temperature error (relative to input range), (+/-) | 0.006 %/K |
Crosstalk between the inputs, min. | 60 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.06% |
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.10% |
Linearity error (relative to output range), (+/-) | 0.15% |
Temperature error (relative to output range), (+/-) | 0.01 %/K |
Crosstalk between the outputs, min. | 60 dB |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.06% |
Operational error limit in overall temperature range | |
● Voltage, relative to input range, (+/-) ● Current, relative to input range, (+/-) ● Resistance, relative to input range, (+/-) ● Voltage, relative to output range, (+/-) ● Current, relative to output range, (+/-) |
1 % 1 % 1 % 1 % 1 % |
Basic error limit (operational limit at 25 °C) | |
● Voltage, relative to input range, (+/-) ● Current, relative to input range, (+/-) ● Resistance, relative to input range, (+/-) ● Resistance thermometer, relative to input range, (+/- ) ● Voltage, relative to output range, (+/-) ● Current, relative to output range, (+/-) |
0.8 %; Linearity error ±0.06 % 0.8 %; Linearity error ±0.06 % 0.8 %; Linearity error ±0.2 % 0.8 % 0.8 % 0.8 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |
● Series mode interference (peak value of interference < rated value of input range), min. ● Common mode interference, min. |
30 dB 40 dB |
Interfaces | |
Number of industrial Ethernet interfaces | 1; 2 ports (switch) RJ45 |
Number of PROFINET interfaces | 1; 2 ports (switch) RJ45 |
Number of RS 485 interfaces | 1; Combined MPI / PROFIBUS DP |
Number of RS 422 interfaces | 0 |
1. Interface | |
Interface type | Integrated RS 485 interface |
Isolated | Yes |
Interface types | |
● RS 485 ● Output current of the interface, max. |
Yes 200 mA |
Protocols | |
● MPI ● PROFIBUS DP master ● PROFIBUS DP slave ● Point-to-point connection |
Yes Yes Yes No |
MPI | |
● Transmission rate, max. | 12 Mbit/s |
Services | |
— PG/OP communication — Routing — Global data communication — S7 basic communication — S7 communication — S7 communication, as client — S7 communication, as server |
Yes Yes Yes Yes Yes No; but via CP and loadable FB Yes |
PROFIBUS DP master | |
● Transmission rate, max. ● Number of DP slaves, max. |
12 Mbit/s 124 |
Services | |
— PG/OP communication — Routing — Global data communication — S7 basic communication — S7 communication — S7 communication, as client — S7 communication, as server — Equidistance — Isochronous mode — SYNC/FREEZE — Activation/deactivation of DP slaves — Number of DP slaves that can be simultaneously activated/deactivated, max. — Direct data exchange (slave-to-slave communication) — DPV1 |
Yes Yes No Yes; I blocks only Yes No Yes Yes No Yes Yes 8 Yes; as subscriber Yes |
Address area | |
— Inputs, max. — Outputs, max. |
2 kbyte 2 kbyte |
User data per DP slave | |
— Inputs, max. — Outputs, max. |
244 byte 244 byte |
PROFIBUS DP slave | |
● Transmission rate, max. ● automatic baud rate search ● Address area, max. ● User data per address area, max. |
12 Mbit/s Yes; only with passive interface 32 32 byte |
Services | |
— PG/OP communication — Routing — Global data communication — S7 basic communication — S7 communication — S7 communication, as client |
Yes Yes; Only with active interface No No Yes No |
— S7 communication, as server — Direct data exchange (slave-to-slave communication) — DPV1 |
Yes; Connection configured on one side only Yes No |
Transfer memory | |
— Inputs — Outputs |
244 byte 244 byte |
2. Interface | |
Interface type | PROFINET |
Isolated | Yes |
automatic detection of transmission rate | Yes; 10/100 Mbit/s |
Autonegotiation | Yes |
Autocrossing | Yes |
Change of IP address at runtime, supported | Yes |
Interface types | |
● RJ 45 (Ethernet) ● Number of ports ● integrated switch |
Yes 2 Yes |
Protocols | |
● MPI ● PROFINET IO Controller ● PROFINET IO Device ● PROFINET CBA ● PROFIBUS DP master ● PROFIBUS DP slave ● Open IE communication ● Web server ● Media redundancy |
No Yes; Also simultaneously with IO-Device functionality Yes; Also simultaneously with IO Controller functionality Yes No No Yes; Via TCP/IP, ISO on TCP, and UDP Yes Yes |
PROFINET IO Controller | |
● Transmission rate, max. | 100 Mbit/s |
Services | |
— PG/OP communication — Routing — S7 communication — Isochronous mode — IRT — Shared device — Prioritized startup — Number of IO devices with prioritized startup, max. — Number of connectable IO Devices, max. — Of which IO devices with IRT, max. — of which in line, max. — Number of IO Devices with IRT and the option "high flexibility" — of which in line, max. — Number of connectable IO Devices for RT, max. — of which in line, max. — Activation/deactivation of IO Devices — Number of IO Devices that can be simultaneously activated/deactivated, max. — IO Devices changing during operation (partner ports), supported — Number of IO Devices per tool, max. — Device replacement without swap medium — Send cycles — Updating time |
Yes Yes Yes; With loadable FBs, max. configurable connections: 10, max. number of instances: 32 Yes; OB 61 Yes Yes Yes 32 128 64 64 128 61 128 128 Yes 8 Yes 8 Yes 250 μs, 500 μs,1 ms; 2 ms, 4 ms (not in the case of IRT with "high flexibility" option) 250 µs to 512 ms (depending on the operating mode, see Manual "S7- 300 CPU 31xC and CPU 31x, technical Data" for more details) |
Address area | |
— Inputs, max. — Outputs, max. — User data consistency, max. |
2 kbyte 2 kbyte 1 024 byte |
PROFINET IO Device | |
Services | |
— PG/OP communication — Routing — S7 communication — Isochronous mode — IRT — PROFIenergy — Shared device — Number of IO Controllers with shared device, max. |
Yes Yes Yes; With loadable FBs, max. configurable connections: 10, max. number of instances: 32 No Yes Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device Yes 2 |
Transfer memory | |
— Inputs, max. — Outputs, max. |
1 440 byte; Per IO Controller with shared device 1 440 byte; Per IO Controller with shared device |
Submodules | |
— Number, max. — User data per submodule, max. |
64 1 024 byte |
PROFINET CBA | |
● acyclic transmission ● cyclic transmission |
Yes Yes |
Open IE communication | |
● Number of connections, max. ● Local port numbers used at the system end ● Keep-alive function, supported |
8 0, 20, 21, 23, 25, 80, 102, 135, 161, 443, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535 Yes |
Protocols | |
PROFIsafe | No |
Redundancy mode | |
Media redundancy | |
— Switchover time on line break, typ. — Number of stations in the ring, max. |
200 ms; PROFINET MRP 50 |
Open IE communication | |
● TCP/IP — Number of connections, max. — Data length for connection type 01H, max. — Data length for connection type 11H, max. — several passive connections per port, supported ● ISO-on-TCP (RFC1006) — Number of connections, max. — Data length, max. ● UDP — Number of connections, max. — Data length, max. |
Yes; via integrated PROFINET interface and loadable FBs 8 1 460 byte 32 768 byte Yes Yes; via integrated PROFINET interface and loadable FBs 8 32 768 byte Yes; via integrated PROFINET interface and loadable FBs 8 1 472 byte |
Web server | |
● supported ● User-defined websites ● Number of HTTP clients |
Yes Yes 5 |
communication functions / header | |
PG/OP communication | Yes |
Data record routing | Yes |
Global data communication | |
● supported ● Number of GD loops, max. ● Number of GD packets, max. ● Number of GD packets, transmitter, max. |
Yes 8 8 8 |
● Number of GD packets, receiver, max. ● Size of GD packets, max. ● Size of GD packet (of which consistent), max. |
8 22 byte 22 byte |
S7 basic communication | |
● supported ● User data per job, max. ● User data per job (of which consistent), max. |
Yes 76 byte 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) |
S7 communication | |
● supported ● as server ● as client ● User data per job, max. |
Yes Yes Yes; via integrated PROFINET interface and loadable FB or via CP and loadable FB See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication) |
S5 compatible communication | |
● supported | Yes; via CP and loadable FC |
communication functions / PROFINET CBA (with set target communication load) / header | |
● Setpoint for the CPU communication load ● number of remote connection partners / with PROFINET CBA ● number of technological functions / with PROFINET CBA / for master or slave ● number of connections / with PROFINET CBA / for master or slave / total ● data volume / of the input variables / with PROFINET CBA / for master or slave ● data volume / of the output variables / with PROFINET CBA / for master or slave ● number of internal and PROFIBUS interconnections / with PROFINET CBA / maximum ● data volume / of internal and PROFIBUS interconnections / with PROFINET CBA / for master or slave ● data volume / with PROFINET CBA / per connection / maximum |
50 % 32 30 1 000 4 000 byte 4 000 byte 500 4 000 byte 1 400 byte |
performance data / PROFINET CBA / remote interconnection / with acyclic transfer / header | |
— update time / of the remote interconnections / in the case of acyclic transmission / with PROFINET CBA — number of remote connections to input variables / in the case of acyclic transmission / with PROFINET CBA / maximum — number of remote connections to output variables / in the case of acyclic transmission / with PROFINET CBA / maximum — data volume / as user data for remote interconnections with input variables / in the case of acyclic transmission / with PROFINET CBA — data volume / as user data for remote interconnections with output variables / in the case of acyclic transmission / with PROFINET CBA — data volume / as user data for remote interconnections / in the case of acyclic transmission / with PROFINET CBA / per connection / maximum |
500 ms 100 100 2 000 byte 2 000 byte 1 400 byte |
performance data / PROFINET CBA / remote interconnection / with cyclic transfer / header | |
— update time / of the remote interconnections / with cyclical transfer / with PROFINET CBA — number of remote connections to input variables / with PROFINET CBA / with cyclic transfer / maximum — number of remote connections to output variables / with cyclical transfer / with PROFINET CBA / maximum — data volume / as user data for remote interconnections with input variables / with cyclical |
10 ms 200 200 2 000 byte |
transfer / with PROFINET CBA / maximum — data volume / as user data for remote interconnections with output variables / with cyclical transfer / with PROFINET CBA / maximum — data volume / as user data for remote interconnections / with cyclical transfer / with PROFINET CBA / per connection / maximum |
2 000 byte 450 byte |
performance data / PROFINET CBA / HMI variables via PROFINET / acyclic / header | |
— number of connectable HMI stations / for HMI variables / in the case of acyclic transmission / with PROFINET CBA — update time / of the HMI variables / in the case of acyclic transmission / with PROFINET CBA — number of HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum — data volume / as user data for HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum |
3; 2x PN OPC/1x iMap 500 ms 200 2 000 byte |
performance data / PROFINET CBA / PROFIBUS proxy functionality / header | |
— product function / with PROFINET CBA / PROFIBUS proxy functionality — number of coupled PROFIBUS devices / with PROFIBUS functionality — data volume / with PROFIBUS proxy functionality / with PROFINET CBA / per connection / maximum |
Yes 16 240 byte; Slave-dependent |
Number of connections | |
● overall ● usable for PG communication — reserved for PG communication — adjustable for PG communication, min. — adjustable for PG communication, max. ● usable for OP communication — reserved for OP communication — adjustable for OP communication, min. — adjustable for OP communication, max. ● usable for S7 basic communication — reserved for S7 basic communication — adjustable for S7 basic communication, min. — adjustable for S7 basic communication, max. ● usable for S7 communication — reserved for S7 communication — adjustable for S7 communication, min. — adjustable for S7 communication, max. ● total number of instances, max. ● usable for routing |
12 11 1 1 11 11 1 1 11 8 0 0 8 10 0 0 10 32 X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as PROFINET: 24 max. |
S7 message functions | |
Number of login stations for message functions, max. | 12; Depending on the configured connections for PG/OP and S7 basic communication |
Process diagnostic messages | Yes |
simultaneously active Alarm-S blocks, max. | 300 |
Test commissioning functions | |
Status block | Yes; Up to 2 simultaneously |
Single step | Yes |
Number of breakpoints | 4 |
Status/control | |
● Status/control variable ● Variables ● Number of variables, max. — of which status variables, max. — of which control variables, max. |
Yes Inputs, outputs, memory bits, DB, times, counters 30 30 14 |
Forcing | |
● Forcing ● Forcing, variables ● Number of variables, max. |
Yes Inputs, outputs 10 |
Diagnostic buffer | |
● present ● Number of entries, max. — adjustable — of which powerfail-proof ● Number of entries readable in RUN, max. — adjustable — preset |
Yes 500 No 100; Only the last 100 entries are retained 499 Yes; From 10 to 499 10 |
Service data | |
● can be read out | Yes |
Interrupts/diagnostics/status information | |
Diagnostics indication LED | |
● Status indicator digital input (green) ● Status indicator digital output (green) |
Yes Yes |
Integrated Functions | |
Counter ● Number of counters ● Counting frequency, max. |
4; See "Technological Functions" manual 60 kHz |
Frequency measurement ● Number of frequency meters |
Yes 4; up to 60 kHz (see "Technological Functions" manual) |
controlled positioning | Yes |
integrated function blocks (closed-loop control) | Yes; PID controller (see "Technological Functions" manual) |
PID controller | Yes |
Number of pulse outputs |
4; Pulse width modulation up to 2.5 kHz (see "Technological Functions" Manual) |
Limit frequency (pulse) | 2.5 kHz |
Potential separation | |
Potential separation digital inputs | |
● Potential separation digital inputs ● between the channels ● between the channels and backplane bus |
Yes No YesYes |
Potential separation digital outputs | |
● Potential separation digital outputs ● between the channels ● between the channels, in groups of ● between the channels and backplane bus |
Yes Yes 8 Yes |
Potential separation analog inputs | |
● Potential separation analog inputs ● between the channels ● between the channels and backplane bus |
Yes; common for analog I/O No Yes |
Potential separation analog outputs | |
● Potential separation analog outputs ● between the channels ● between the channels and backplane bus |
Yes; common for analog I/O No Yes |
Isolation | |
Isolation tested with | 600 V DC |
Ambient conditions | |
Ambient temperature during operation | |
● min. ● max. |
0 °C 60 °C |
configuration / header | |
Configuration software | |
● STEP 7 | Yes; V5.5 or higher |
configuration / programming / header | |
● Command set ● Nesting levels |
see instruction list 8 |
● System functions (SFC) ● System function blocks (SFB) |
see instruction list see instruction list |
Programming language | |
— LAD — FBD — STL — SCL — CFC — GRAPH — HiGraph® |
Yes Yes Yes Yes Yes Yes Yes |
Know-how protection | |
● User program protection/password protection ● Block encryption |
Yes Yes; With S7 block Privacy |
Dimensions | |
Width |
120 mm |
Height | 125 mm |
Depth | 130 mm |
Weights | |
Weight, approx. | 730 g |
6ES7314-6EH04-0AB0 | 6ES7313-6BG04-0AB0 | 6ES7318-3EL01-0AB0 |
6ES7317-2EK14-0AB0 | 6ES7317-2AK14-0AB0 | 6ES7315-2EH14-0AB0 |
6ES7313-6CG04-0AB0 | 6ES7314-6BH04-0AB0 | 6ES7312-1AE14-0AB0 |
6ES7313-5BG04-0AB0 | 6ES7315-2AH14-0AB0 | 6ES7314-6CH04-0AB0 |
6ES7314-1AG14-0AB0 | 6ES7312-5BF04-0AB0 | 6ES7314-6EH04-4AB2 |
6ES7313-6CG04-4AB2 | 6ES7314-6CH04-4AB1 | 6ES7313-5BG04-4AB1 |
6ES7315-2EH14-0AB0 | 6ES7313-5BG04-4AB2 | 6ES7317-2EK14-0AB0 |
6ES7314-1AG14-0AB0 | 6ES7314-6CH04-4AB2 | 6ES7313-6CG04-4AB1 |
6ES7314-6EH04-4AB1 | 6ES7312-1AE14-0AB0 | 6ES7312-5BF04-0AB0 |
6ES7313-5BG04-4AB1 | 6ES7313-5BG04-4AB2 | 6ES7313-6BG04-0AB0 |
6ES7313-6CG04-4AB1 | 6ES7313-6CG04-4AB2 | 6ES7314-1AG14-0AB0 |
6ES7314-6BH04-0AB0 | 6ES7314-6CH04-4AB1 | 6ES7314-6CH04-4AB2 |
6ES7314-6EH04-4AB1 | 6ES7314-6EH04-4AB2 | 6ES7315-2AH14-0AB0 |
6ES7315-2EH14-0AB0 | 6ES7317-2AK14-0AB0 | 6ES7317-2EK14-0AB0 |
6ES7318-3EL01-0AB0 |