SIPLUS S7-300 SM 331 8AI 40-pole based on 6ES7331-7PF11-0AB0 with conformal coating, 0…+60 °C, analog input isolated, 8 AI thermocouples type B, E, J, K, L, N, R, S, T TXK/TXK (L) according to GOST 16-bit, 50 ms, 1x 40-pole
SIPLUS S7-300 SM 331 8AI 40-pole based on 6ES7331-7PF11-0AB0 with conformal coating, 0…+60 °C, analog input isolated, 8 AI thermocouples type B, E, J, K, L, N, R, S, T TXK/TXK (L) according to GOST 16-bit, 50 ms, 1x 40-pole
Supply voltage | |||
Load voltage L+ | |||
● Rated value (DC) | 24 V | ||
● Reverse polarity protection | Yes | ||
Input current | |||
from load voltage L+ (without load), max. | 240 mA | ||
from backplane bus 5 V DC, max. | 100 mA | ||
Power loss | |||
Power loss, typ. | 3 W | ||
Analog inputs | |||
Number of analog inputs | 8 | ||
permissible input voltage for voltage input (destruction limit), max. | 75 V; 20 V DC permanent, 75 V DC for max. 1 s (duty factor 1:20) | ||
Constant measurement current for resistance-type transmitter, typ. | 0.7 mA | ||
Input ranges | |||
● Voltage | No | ||
● Current | No | ||
● Thermocouple | Yes | ||
● Resistance thermometer | No | ||
● Resistance | No | ||
Input ranges (rated values), voltages | |||
● 0 to +10 V | No | ||
● 1 V to 5 V | No | ||
● 1 V to 10 V | No | ||
● -1 V to +1 V | No | ||
● -10 V to +10 V | No | ||
● -2.5 V to +2.5 V | No | ||
● -250 mV to +250 mV | No | ||
● -5 V to +5 V | No | ||
● -50 mV to +50 mV | No | ||
● -500 mV to +500 mV | No | ||
● -80 mV to +80 mV | No | ||
Input ranges (rated values), currents | |||
● 0 to 20 mA | No | ||
● -10 mA to +10 mA | No | ||
● -20 mA to +20 mA | No | ||
● -3.2 mA to +3.2 mA | No | ||
● 4 mA to 20 mA | No | ||
Input ranges (rated values), thermocouples | |||
● Type B ● Type C ● Type E ● Type J ● Type K ● Type L ● Type N ● Type R ● Type S ● Type T ● Type U ● Type TXK/TXK(L) to GOST |
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes |
||
Input ranges (rated values), resistance thermometer | |||
● Cu 10 ● Ni 100 ● Ni 1000 ● LG-Ni 1000 ● Ni 120 ● Ni 200 ● Ni 500 ● Pt 100 ● Pt 1000 ● Pt 200 ● Pt 500 |
No No No No No No No No No No No |
||
Input ranges (rated values), resistors | |||
Thermocouple (TC) | |||
Temperature compensation | |||
— parameterizable — internal temperature compensation — external temperature compensation with Pt100 — external temperature compensation with compensations socket — for definable comparison point temperature |
Yes Yes Yes Yes Yes |
||
Characteristic linearization | |||
● parameterizable — for thermocouples |
Yes Type B, E, J, K, L, N, R, S. T, U, C |
||
Cable length | |||
Analog value generation for the inputs | |||
Integration and conversion time/resolution per channel | |||
Interrupts/diagnostics/status information | |||
Diagnostics function | Yes; Parameterizable | ||
Alarms | |||
● Diagnostic alarm ● Limit value alarm ● Hardware interrupt |
Yes; Parameterizable per group Yes; Parameterizable Yes; Parameterizable, channels 0 to 7 |
||
Diagnoses | |||
● Diagnostic information readable | Yes | ||
Diagnostics indication LED | |||
● Group error SF (red) | Yes | ||
Potential separation | |||
Potential separation analog inputs | |||
● between the channels ● between the channels, in groups of ● between the channels and backplane bus ● between the channels and the power supply of the electronics |
No 2 Yes Yes |
||
Isolation | |||
Isolation tested with | 500 V DC | ||
Standards, approvals, certificates | |||
CE mark | Yes | ||
UL approval | Yes; File E239877 | ||
RCM (formerly C-TICK) | Yes | ||
KC approval | Yes | ||
EAC (formerly Gost-R) | Yes | ||
Railway application | |||
● EN 50121-4 ● EN 50155 |
No No |
||
Ambient conditions | |||
Ambient temperature during operation | |||
● min. ● max. |
0 °C; = Tmin 60 °C; = Tmax |
||
Ambient temperature during storage/transportation | |||
● min. ● max. |
-40 °C 70 °C |
||
Altitude during operation relating to sea level | |||
● Installation altitude above sea level, max. ● Ambient air temperature-barometric pressure- altitude |
5 000 m Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
||
Relative humidity | |||
● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | ||
Resistance | |||
Use in stationary industrial systems | |||
— to biologically active substances according to EN 60721-3-3 — to chemically active substances according to EN 60721-3-3 — to mechanically active substances according to EN 60721-3-3 |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * Yes; Class 3S4 incl. sand, dust, * |
||
Use on ships/at sea | |||
— to biologically active substances according to EN 60721-3-6 — to chemically active substances according to EN 60721-3-6 — to mechanically active substances according to EN 60721-3-6 |
Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * Yes; Class 6S3 incl. sand, dust; * |
||
Usage in industrial process technology | |||
— Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) | ||
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA- 71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) | ||
Remark | |||
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! | ||
connection method / header | |||
required front connector | 40-pin | ||
Dimensions | |||
Width | 40 mm | ||
Height | 125 mm | ||
Depth | 100mm | ||
Weights | |||
Weight, approx. | 272 g |
6AG1332-5HB01-2AB0 | 6AG1313-5BG04-7AB0 | 6AG1321-1FF10-7AA0 |
6AG1313-6CG04-2AY0 | 6AG1331-7NF00-2AB0 | 6AG1322-1BL00-2AA0 |
6AG1350-1AH03-2AE0 | 6AG1314-6CH04-7AB0 | 6AG1331-7TB00-7AB0 |
6AG1332-7ND02-4AB0 | 6AG1341-1CH02-7AE0 | 6AG1322-1FF01-7AA0 |
6AG1322-1BH01-2AA0 | 6AG1314-6CH04-2AY0 | 6AG1312-5BF04-7AB0 |
6AG1350-2AH01-4AE0 | 6AG1321-1FH00-7AA0 | 6AG1331-7SF00-4AB0 |
6AG1317-2EK14-7AB0 | 6AG1314-1AG14-7AB0 | 6AG1315-2EH14-7AB0 |
6AG1341-1AH02-7AE0 | 6AG1322-5FF00-4AB0 | 6AG1321-7RD00-4AB0 |
6AG1312-5BF04-2AY0 | 6AG1334-0KE00-7AB0 | 6AG1314-6EH04-7AB0 |
6AG1313-6CG04-7AB0 | 6AG1331-7RD00-2AB0 | 6AG1322-1BF01-2XB0 |
6AG1322-1FH00-7AA0 | 6AG1315-2EH14-2AY0 | 6AG1317-2EK14-2AY0 |
6AG1332-5HF00-2AB0 | 6AG1321-1FF01-2AA0 | 6AG1331-7PF11-4AB0 |
6AG1313-5BG04-2AY0 | 6AG1321-7BH01-4AS0 | 6AG1340-1AH02-2AE0 |
6AG1315-2AH14-7AB0 | 6AG1332-5HD01-7AB0 | 6AG1340-1CH02-2AE0 |
6AG1314-6BH04-7AB0 |