Model Number: 6AG1315-2EH14-7AB0 6AG1341-1AH02-7AE0 6AG1322-5FF00-4AB0 6AG1321-7RD00-4AB0 6AG1312-5BF04-2AY0 Category: SIEMENS SIPLUS S7300 Product Type: PLC Type: Industry Automation Place of Origin: Made in Germany Warranty: 12 month warranty
SIPLUS S7-300 CPU 315-2PN/DP based on 6ES7315-2EH14-0AB0 with conformal coating, -25…+70 °C, central processing unit with 384 KB work memory, 1st interface MPI/DP 12 Mbps, 2nd interface Ethernet PROFINET, with 2-port switch, Micro Memory Card required
SIPLUS S7-300 CPU 315-2PN/DP based on 6ES7315-2EH14-0AB0 with conformal coating, -25…+70 °C, central processing unit with 384 KB work memory, 1st interface MPI/DP 12 Mbps, 2nd interface Ethernet PROFINET, with 2-port switch, Micro Memory Card required
| Supply voltage | |
| Auxiliary voltage 1L+, load voltage 2L+ | |
|
● Rated value (DC) ● permissible range, lower limit (DC) ● permissible range, upper limit (DC) |
24 V 20.4 V 28.8 V |
| Input current | |
| from load voltage L+ (without load), max. | 150 mA |
| from backplane bus 5 V DC, max. | 100 mA |
| Encoder supply | |
| NAMUR encoder supply | |
|
● 8.2 V ● Short-circuit protection ● Output current, max. |
Yes Yes 200 mA |
| Power loss | |
| Power loss, typ. | 10 W |
| Digital inputs | |
| Number of digital inputs | 8 |
| Number of NAMUR inputs | 8 |
| Functions | 1 each for gate start/ gate stop |
| Input voltage | |
|
● for signal "0" ● for signal "1" |
-3 to +5V 11 to 30.2 V |
| Input current | |
|
● for signal "0", max. (permissible quiescent current) ● for signal "1", typ. |
2 mA 9 mA |
| Input delay (for rated value of input voltage) | |
| ● Input frequency, max. | 20 kHz |
| for standard inputs | |
| — at "0" to "1", max. | 50 µs |
| for NAMUR inputs | |
| — at "0" to "1", max. | 50 µs |
| Cable length | |
| ● shielded, max. | 100 m |
| Digital outputs | |
| Number of digital outputs | 8 |
| Short-circuit protection | Yes |
| Limitation of inductive shutdown voltage to | L+ (-40 V) |
| Output voltage | |
| ● for signal "1", min. | L+ (-0.8 V) |
| Output current | |
|
● for signal "1" rated value ● for signal "0" residual current, max. |
0.5 A 0.5 mA |
| Output delay with resistive load | |
| ● "0" to "1", max. | 300 µs |
| Switching frequency | |
|
● with resistive load, max. ● with inductive load, max. |
500 Hz 0.5 Hz |
| Total current of the outputs (per group) | |
| horizontal installation | |
|
— up to 40 °C, max. — up to 60 °C, max. |
4 A 2 A |
| all other mounting positions | |
| — up to 40 °C, max. | 2 A |
| Cable length | |
|
● shielded, max. ● unshielded, max. |
600 m 100 m |
| Encoder | |
| Connectable encoders | |
|
● Incremental encoder (asymmetrical) ● 24 V initiator ● 24 V directional element ● NAMUR encoder ● 2-wire sensor |
Yes Yes Yes Yes; to DIN 19 234 Yes |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes; Diagnostic information readable |
| Alarms | |
|
● Diagnostic alarm ● Hardware interrupt |
Yes; Parameterizable Yes; Parameterizable |
| Diagnostics indication LED | |
| ● Group error SF (red) | Yes |
| Counter | |
| Number of counter inputs | 8; 32 bit or ±31 bit |
| Counter input 24 V | |
|
● Input voltage for signal "0" ● Input voltage for signal "1" ● Input current for signal "1", typ. ● Counting frequency, max. |
-3 to +5V 11 to 30.2 V 9 mA 20 kHz; Incremental encoder: 10 kHz |
| Potential separation | |
| Potential separation digital inputs | |
| ● between the channels and backplane bus | Yes; and shielding |
| Potential separation digital outputs | |
| ● between the channels and backplane bus | Yes; and shielding |
| Potential separation counter | |
| ● between the channels and backplane bus | Yes; and shielding |
| Standards, approvals, certificates | |
| CE mark | Yes |
| UL approval | Yes; File E239877 |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| EAC (formerly Gost-R) | Yes |
| Ambient conditions | |
| Ambient temperature during operation | |
|
● min. ● max. |
0 °C; = Tmin 60 °C; = Tmax |
| Altitude during operation relating to sea level | |
|
● Installation altitude above sea level, max. ● Ambient air temperature-barometric pressure- |
5 000 m Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin |
| altitude |
... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| ● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Use in stationary industrial systems | |
|
— to biologically active substances according to EN 60721-3-3 — to chemically active substances according to EN 60721-3-3 — to mechanically active substances according to EN 60721-3-3 |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * Yes; Class 3S4 incl. sand, dust, * |
| Use on ships/at sea | |
|
— to biologically active substances according to EN 60721-3-6 — to chemically active substances according to EN 60721-3-6 — to mechanically active substances according to EN 60721-3-6 |
Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
|
— Against chemically active substances acc. to EN 60654-4 — Environmental conditions for process, measuring and control systems acc. to ANSI/ISA- 71.04 |
Yes; Class 3 (excluding trichlorethylene) Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| — Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| connection method / header | |
| required front connector | 1x 40-pin |
| Dimensions | |
| Width | 80 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 460 g |
| 6AG1332-5HB01-2AB0 | 6AG1313-5BG04-7AB0 | 6AG1321-1FF10-7AA0 |
| 6AG1313-6CG04-2AY0 | 6AG1331-7NF00-2AB0 | 6AG1322-1BL00-2AA0 |
| 6AG1350-1AH03-2AE0 | 6AG1314-6CH04-7AB0 | 6AG1331-7TB00-7AB0 |
| 6AG1332-7ND02-4AB0 | 6AG1341-1CH02-7AE0 | 6AG1322-1FF01-7AA0 |
| 6AG1322-1BH01-2AA0 | 6AG1314-6CH04-2AY0 | 6AG1312-5BF04-7AB0 |
| 6AG1350-2AH01-4AE0 | 6AG1321-1FH00-7AA0 | 6AG1331-7SF00-4AB0 |
| 6AG1317-2EK14-7AB0 | 6AG1314-1AG14-7AB0 | 6AG1315-2EH14-7AB0 |
| 6AG1341-1AH02-7AE0 | 6AG1322-5FF00-4AB0 | 6AG1321-7RD00-4AB0 |
| 6AG1312-5BF04-2AY0 | 6AG1334-0KE00-7AB0 | 6AG1314-6EH04-7AB0 |
| 6AG1313-6CG04-7AB0 | 6AG1331-7RD00-2AB0 | 6AG1322-1BF01-2XB0 |
| 6AG1322-1FH00-7AA0 | 6AG1315-2EH14-2AY0 | 6AG1317-2EK14-2AY0 |
| 6AG1332-5HF00-2AB0 | 6AG1321-1FF01-2AA0 | 6AG1331-7PF11-4AB0 |
| 6AG1313-5BG04-2AY0 | 6AG1321-7BH01-4AS0 | 6AG1340-1AH02-2AE0 |
| 6AG1315-2AH14-7AB0 | 6AG1332-5HD01-7AB0 | 6AG1340-1CH02-2AE0 |
| 6AG1314-6BH04-7AB0 |